A complete reference for Samsung EHS heat pump Field Setting Values. FSVs are installer-level configuration parameters that control temperature limits, weather curves, DHW behaviour, backup heater logic, and more.
Field Setting Values (FSVs) are configuration parameters stored in the wired remote controller of Samsung EHS heat pumps. They are typically set by the installer during commissioning and control fundamental aspects of how the heat pump operates. FSVs are organised into five categories, each identified by a number prefix.
Controls the upper and lower temperature limits that a user can set on the wired remote controller for each operating mode. Adjusting these lets an installer restrict or expand the temperature range available to the end user.
Sets the allowed range for the target water outlet temperature during cooling mode.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #1011 | Upper limit | °C | 25 | 18 | 25 |
| #1012 | Lower limit | °C | 16 | 5 | 18 |
Sets the allowed range for the target room temperature during cooling mode.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #1021 | Upper limit | °C | 30 | 28 | 30 |
| #1022 | Lower limit | °C | 18 | 18 | 28 |
Sets the allowed range for the target water outlet temperature during heating mode. This is one of the most important FSV groups — it determines what flow temperatures your system can target.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #1031 | Upper limit | °C | 70 | 37 | 70 |
| #1032 | Lower limit | °C | 25 | 15 | 37 |
Sets the allowed range for the target room temperature during heating mode.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #1041 | Upper limit | °C | 30 | 18 | 30 |
| #1042 | Lower limit | °C | 16 | 16 | 18 |
Sets the allowed range for the target domestic hot water (DHW) tank temperature.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #1051 | Upper limit | °C | 55 | 50 | 70 |
| #1052 | Lower limit | °C | 40 | 30 | 40 |
Weather-dependent control that automatically adjusts the water outlet temperature based on the outdoor air temperature. This reduces unnecessary energy consumption by lowering the flow temperature when it's warmer outside. Also known as a “weather curve” or “heating curve”.
Defines the outdoor air temperature range over which the heating water law curve operates. The curve maps between two points: a cold outdoor temp (Point ②) with a high water temp, and a warm outdoor temp (Point ①) with a low water temp.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #2011 | Lower outdoor temp (Point ②) | °C | -10 | -20 | 5 |
| #2012 | Upper outdoor temp (Point ①) | °C | 15 | 10 | 20 |
Water law curve target temperatures for WL1 (underfloor heating). At the lower outdoor temp, the system targets the higher water temp; at the upper outdoor temp, it targets the lower water temp.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #2021 | Water temp at cold outdoor (Point ①) | °C | 40 | 17 | 65 |
| #2022 | Water temp at warm outdoor (Point ②) | °C | 25 | 17 | 65 |
Water law curve target temperatures for WL2 (fan coil units or radiators). Radiators and FCUs typically need higher water temperatures than underfloor heating.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #2031 | Water temp at cold outdoor (Point ①) | °C | 50 | 17 | 65 |
| #2032 | Water temp at warm outdoor (Point ②) | °C | 35 | 17 | 65 |
Selects which water law curve to use for heating mode.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #2041 | WL type for heating | — | 1 (WL1 — floor) | 1 | 2 |
Defines the outdoor air temperature range for the cooling water law curve.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #2051 | Lower outdoor temp (Point ①) | °C | 30 | 25 | 35 |
| #2052 | Upper outdoor temp (Point ②) | °C | 40 | 35 | 45 |
Water law curve target temperatures for cooling via underfloor heating.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #2061 | Water temp at warm outdoor (Point ①) | °C | 25 | 5 | 25 |
| #2062 | Water temp at cold outdoor (Point ②) | °C | 18 | 5 | 25 |
Water law curve target temperatures for cooling via fan coil units.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #2071 | Water temp at warm outdoor (Point ①) | °C | 18 | 5 | 25 |
| #2072 | Water temp at cold outdoor (Point ②) | °C | 5 | 5 | 25 |
Selects which water law curve to use for cooling mode.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #2081 | WL type for cooling | — | 1 (WL1 — floor) | 1 | 2 |
Configures external room thermostat inputs. When enabled, an external thermostat can control the compressor and water pump based on room temperature demand.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #2091 | Thermostat #1 (UFH zone) | — | 0 (No) | 0 | 4 |
| #2092 | Thermostat #2 (FCU zone) | — | 0 (No) | 0 | 4 |
| #2093 | Remote controller room temp control | — | 4 | 1 | 4 |
Controls all aspects of domestic hot water production including heat pump and booster heater behaviour, tank disinfection, and forced DHW operation.
Enables or disables DHW functionality and controls how DHW heating starts and stops.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #3011 | DHW application mode | — | 1 (Yes) | 0 | 2 |
Controls the heat pump’s thermo on/off behaviour during DHW operation and the timing between DHW and space heating.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #3021 | Max HP temperature for DHW | °C | 55 | 45 | 55 |
| #3022 | Temp diff for HP OFF (relative to max HP temp or set temp) | °C | 0 | 0 | 10 |
| #3023 | Temp diff for HP ON (relative to HP OFF temp) | °C | 5 | 5 | 30 |
| #3024 | Min space heating operation time | min | 5 | 1 | 20 |
| #3025 | Max DHW operation time | min | 30 | 5 | 95 |
| #3026 | Max space heating operation time after DHW | hr | 3 | 0.5 | 10 |
Controls the electric booster heater (immersion) in the DHW tank. The booster heater supplements the heat pump when higher tank temperatures are needed.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #3031 | Booster heater application | — | 1 (On) | 0 | 1 |
| #3032 | Startup delay time | min | 20 | 20 | 95 |
| #3033 | Overshoot (temp above set temp for BSH OFF) | °C | 0 | 0 | 4 |
Periodically heats the DHW tank to a high temperature to kill legionella and other bacteria. This uses the booster heater to reach temperatures above what the heat pump alone can achieve.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #3041 | Application | — | 1 (On) | 0 | 1 |
| #3042 | Day of week (0=Sun, 1=Mon, … 6=Sat, 7=Every day) | day | 5 (Fri) | 0 (Sun) | 7 (All) |
| #3043 | Start time (hour of day) | hour | 23 | 0 | 23 |
| #3044 | Target temperature | °C | 70 | 40 | 70 |
| #3045 | Hold duration (time at target temp) | min | 10 | 5 | 60 |
| #3046 | Max total time allowed for disinfection cycle | hr | 8 | 1 | 24 |
Controls whether forced DHW mode has a timer that automatically ends the operation.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #3051 | Timer OFF function | — | 0 (No) | 0 | 1 |
| #3052 | Timer duration | ×10 min | 6 (60 min) | 3 (30 min) | 30 (300 min) |
Configures solar panel integration for DHW heating.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #3061 | Solar panel application | — | 0 (No) | 0 | 2 |
Sets the default resting position of the 3-way diverter valve.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #3071 | Default direction | — | 0 (Room) | 0 | 1 |
Sets the rated capacities of the backup heater (BUH) and booster heater (BSH) for accurate energy consumption calculations on the controller display.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #3081 | BUH step 1 capacity | kW | 2 | 1 | 6 |
| #3082 | BUH step 2 capacity | kW | 2 | 0 | 6 |
| #3083 | BSH capacity | kW | 3 | 1 | 6 |
Controls the heat pump’s space heating behaviour, backup heater operation, external backup boiler, mixing valve, inverter pump, and zone control.
Configures heat pump priority between DHW and space heating, and the outdoor temperature at which heating stops.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #4011 | Heating / DHW priority | — | 0 (DHW) | 0 | 1 |
| #4012 | Outdoor temp for priority changeover | °C | 0 | -15 | 20 |
| #4013 | Heat OFF outdoor temp (HP stops heating above this) | °C | 35 | 14 | 35 |
Configures the electric backup heater (BUH) built into the hydro unit. The BUH provides supplemental heating when the heat pump alone cannot meet demand, particularly in very cold weather or during defrost cycles.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #4021 | Application | — | 0 (No) | 0 | 2 |
| #4022 | BUH / BSH priority | — | 2 (BSH) | 0 | 2 |
| #4023 | Cold weather compensation | — | 1 (Yes) | 0 | 1 |
| #4024 | Threshold outdoor temp for BUH | °C | 0 | -25 | 35 |
| #4025 | Defrost backup temp (BUH activates below this water temp during defrost) | °C | 15 | 10 | 55 |
Configures an external backup boiler (e.g. gas or oil) that can take over heating when outdoor temperatures are extremely low.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #4031 | Application | — | 0 (No) | 0 | 1 |
| #4032 | Boiler priority | — | 0 (No) | 0 | 1 |
| #4033 | Threshold outdoor temp | °C | -15 | -20 | 5 |
Configures an optional mixing valve installation, typically used with underfloor heating to blend high-temperature water down to a safe floor temperature.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #4041 | Application | — | 0 (No) | 0 | 2 |
| #4042 | Target ΔT for heating | °C | 10 | 5 | 15 |
| #4043 | Target ΔT for cooling | °C | 10 | 5 | 15 |
| #4044 | Control factor (higher = faster response) | — | 2 | 1 | 5 |
| #4045 | Control interval | min | 2 | 1 | 30 |
| #4046 | Running time | ×10 sec | 9 (90 sec) | 6 (60 sec) | 24 (240 sec) |
Configures the built-in variable-speed circulation pump. The pump adjusts its speed to maintain a target temperature difference (ΔT) between inlet and outlet water.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #4051 | Application | — | 1 (Yes) | 0 | 2 |
| #4052 | Target ΔT | °C | 5 | 2 | 8 |
| #4053 | Control factor | — | 2 | 1 | 3 |
Enables 2-zone control via the wired remote controller, allowing independent control of two heating/cooling zones (e.g. underfloor + radiators).
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #4061 | Application | — | 0 (No) | 0 | 1 |
Miscellaneous settings including outing/holiday mode temperatures, DHW energy saving, power peak control, frequency ratio limiting, PV panel integration, and smart grid control.
Sets the target temperatures for all modes when the system is placed into outing/holiday mode. These are typically set lower than normal to save energy while preventing freezing.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #5011 | Water outlet temp for cooling | °C | 25 | 5 | 25 |
| #5012 | Room temp for cooling | °C | 30 | 18 | 30 |
| #5013 | Water outlet temp for heating | °C | 15 | 15 | 55 |
| #5014 | Room temp for heating | °C | 16 | 16 | 30 |
| #5015 | Auto cooling WL1 temp | °C | 25 | 5 | 25 |
| #5016 | Auto cooling WL2 temp | °C | 25 | 5 | 25 |
| #5017 | Auto heating WL1 temp | °C | 15 | 15 | 55 |
| #5018 | Auto heating WL2 temp | °C | 15 | 15 | 55 |
| #5019 | Target tank temp (DHW) | °C | 30 | 30 | 70 |
Energy-saving mode for DHW that lowers the target tank temperature. Activated via the “Eco” mode on the wired remote controller.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #5021 | Temperature reduction from user setpoint | °C | 5 | 0 | 40 |
| #5022 | DHW saving mode | — | 0 | 0 | 1 |
| #5023 | Thermo-on temp in saving mode | °C | 25 | 0 | 40 |
Allows an external signal (e.g. from a power company) to force certain components off during grid peak demand periods. The signal is applied via a digital input.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #5041 | Application | — | 0 (No) | 0 | 1 |
| #5042 | Select forced-off parts | — | 0 (All heaters off) | 0 | 3 |
| #5043 | Input voltage type | — | 1 (High) | 0 | 1 |
Limits the maximum compressor frequency of the outdoor unit. Can be controlled by a 0–10V DC signal or via Modbus communication. Also known as “Demand Ratio” (DR) on the controller display.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #5051 | Application | — | 0 (Disable) | 0 | 1 |
Controls the capacity ratio between space heating and DHW operations.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #5061 | Heat/DHW capacity ratio | — | — | — | — |
When a solar PV panel system signals that excess energy is available, the heat pump can take advantage by shifting setpoints to store more thermal energy. Shares the same input contact as Power Peak Control, so they cannot both be used.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #5081 | Application | — | 0 (No) | 0 | 1 |
| #5082 | Temp shift for cooling | °C | 1 | 0 | 5 |
| #5083 | Temp shift for heating | °C | 1 | 0 | 5 |
Advanced grid-interactive control using two digital inputs providing four operating modes. Allows power companies to remotely adjust system demand based on grid conditions — both reducing demand during peak load and increasing it when excess grid capacity is available.
| FSV | Description | Unit | Default | Min | Max |
|---|---|---|---|---|---|
| #5091 | Application | — | 0 (No) | 0 | 1 |
| #5092 | Temp shift for heating (step-up) | °C | 2 | 2 | 5 |
| #5093 | Temp shift for DHW (step-up) | °C | 5 | 2 | 5 |
| #5094 | DHW mode for Mode 4 | — | 0 | 0 | 1 |
Important notes